Resolution 224-20151
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
MONROE COUNTY, FLORIDA
MONROE COUNTY BOARD OF COUNTY COMMISSIONERS
RESOLUTION NO. 224 - 2015
A RESOLUTION OF THE MONROE COUNTY BOARD OF
COUNTY COMMISSIONERS ADOPTING FEMA TECHNICAL
BULLETIN 1 "OPENINGS IN FOUNDATION WALLS AND
WALLS OF ENCLOSURES" DATED AUGUST 2008 AS
REQUIRED PURSUANT TO MONROE COUNTY CODE
SECTION 122 -2(C)
WHEREAS, Monroe County is currently a participating community in the National
Flood Insurance Program (NFIP) and is working on internal County policies to improve upon its
interpretation of NFIP regulations; and
WHEREAS, Monroe County desires to become eligible to enter FEMA's Community
Rating System (CRS); and
WHEREAS, Monroe County Code Section 122 -2(c), in part, requires that in interpreting
other provisions of this chapter, the building official shall be guided by the current edition of
FEMA's 44 CFR, and FEMA's interpretive letters, policy statements and technical bulletins as
adopted by resolution from time to time by the board of county commissioners;
NOW, THEREFORE, BE IT RESOLVED BY THE BOARD OF COUNTY
COMMISSIONERS OF MONROE COUNTY, FLORIDA:
Section 1. Pursuant to Monroe County Code Section 122 -2(c), the Board hereby adopts
FEMA Technical Bulletin 1 "Openings in Foundation Walls and Walls of Enclosures" dated
August 2008, a copy of which is attached hereto.
Section 2. The Clerk of the Board is hereby directed to forward one (1) certified copy of
this Resolution to the Building Department.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
BOARD OF COUNTY COMMISSIONERS
OF MONROE COUNTY ,F FLORIDA
BY: - ; okf�
Mayor . Kolhage
MONROE COUNTY ATTORNEY
ROYS D AS nF 0 R M:
STEVEN T. WILLIAMS
ASSISTANT O TY ATTORNEY
Date ,�
PASSED AND ADOPTED by the Board of County Commissioners of Monroe County,
Florida, at a regular meeting held on the 16 of September, 2015.
Mayor Danny L. Kolhage
Yes
Mayor pro tem Heather Carruthers
Yes
Commissioner Sylvia Murphy
Yes
Commissioner George Neugent
Yes
Commissioner David Rice
Yes
_ri iiii„., Tr____ ________
ir--- - -- 7 _,....
1r ,........
r l i i
r . E .....-------1 ri
wommosisommluss
"1/� M
N1 _ _ Ice�,
II
- / r -
;.,
•
i- . 4,__ , i...) ii _ .
•
_ -ill' _� ^ ,�
s P: � zzr r .fir tr
f � .., • _ " '''-ww•-^,7,--,, . ,-,,.- may- _ _ t.. �'
'11
+ „_a
'_ +•�a:- .- -. ..---;'- Si. �4'`'�t tea sr- -. _ . ... 1_, e a
Openings nin In Foundation
Walls and Walls of
Enclosures
Below Elevated Buildings in Special Flood Hazard Areas
in accordance with the National Flood Insurance Program
Technical Bulletin 1 / August 2008
r
�f FEMA
4'4qND 5S
Table of Contents
Introduction.............. ...............................
NFIPRegulations ......................................... ...............................
How Openings Affect Flood Insurance Rates ............................
Documenting Elevations and Information About Openings ...
Enclosed Areas Below Elevated Buildings ... ...............................
Enclosures That Require Openings . ...............................
Situations That Do Not Require Openings ....................
Requirements and Guidance for Installation of Openings.......
Minimum Number of Openings ...... ...............................
Height of Openings Above Grade ... ...............................
Installation Examples ....................... ...............................
Non - Engineered Openings and Engineered Openings............
Unacceptable Measures .................... ...............................
Non- Engineered Openings .............. ...............................
Engineered Openings ...................... ...............................
TheNFIP ....................................................... ...............................
NFIP Technical Bulletins ............................. ...............................
Ordering Technical Bulletins ...................... ...............................
Further Information .................................... ...............................
Glossary............................ ...............................
ell
..28
..29
..30
Comments on the Technical Bulletins should be directed to:
Department of Homeland Security
FEMA Mitigation Directorate
500 C Street, SW.
Washington, D.C. 20472
Technical Bulletin 1 -08 replaces Technical Bulletin 1 -93, Openings in Foundation Walls.
Photograph Credits:
....... ..............................1
....... ..............................4
....... ..............................4
....... ..............................5
..
....... ............................... 6
....... .............................12
....... .............................13
....... .............................13
....... .............................14
....... .............................15
.............18
.............19
.............20
.............24
.............28
Figure 3. Bill Bryant, Anne Arundel County, Maryland
Figure 4. Smart Vent, Inc.
Figure 17. North Carolina Emergency Management/T. Riddle
Introduction
Protecting buildings that are constructed in special flood hazard areas (SFH.As) from dam-
age caused by flood forces is an important objective of the National Flood Insurance Program
(NFIP). In support of this objective, the NFIP regulations include minimum building de-
sign criteria that apply to new construction, repair of substantially damaged buildings, and
substantial improvement of existing buildings in SFHAs. The base flood is used to delineate
SFHAs on Flood Insurance Rate Maps (FIRMs) prepared by the NEW The base flood is the
flood that has a 1- percent chance of being equaled or exceed-
ed in any given year (commonly called the "100- year" flood).
Certain terms used in this Technical Bulletin are defined in
the Glossary.
The NFIP regulations require that residential buildings
constructed in A zones have the lowest floor (including base-
ment) elevated to or above the base flood elevation (BFE). hn
this Technical Bulletin, the term ".A zones" includes all zones
shown on FIRMs as Zones A, AE, Al -A30, AR, AO, and AH.
Enclosed areas (enclosures) are permitted under elevated
buildings provided the enclosed areas meet certain use re-
strictions and construction requirements related to flood
resistance, including use of flood damage - resistant materials
and installation of openings to allow for automatic entry and
exit of floodwaters. Enclosures under buildings in V zones
(includes all Zones V, VE, and Vl-V30) must meet the same en-
closure requirements except that openings are not required
and walls must be non - supporting breakawav walls, open lat-
tice -work, or insect screening (see Technical Bulletin 9, Design.
and Construction Guidance for Breakaway Walls Below F,levated
Coastal Buildings).
The NFIP regulations for new construction and substantial
improvements of existing buildings require that enclosed ar-
eas under elevated non - residential buildings meet the same
requirements as those for enclosures under elevated residen-
tial buildings. New non - residential buildings constructed in A
zones, and substantial improvements of existing non- residen-
tial buildings, must either have their lowest floors elevated to
or above the BFE or be floodproofed (made watertight) to or
above the BFE.
Manv types of foundations are used to elevate buildings. While
the main portions of elevated buildings are above the BFE,
the fotuidation and any enclosed areas below the BFE will
be exposed to flood forces. Enclosed areas below the BFE
Under the NFIP, the "low-
est floor" is the floor of the
lowest enclosed area of
a building. An unfinished
or flood- resistant enclo-
sure that is used solely for
parking of vehicles, build-
ing access, or storage is
not the lowest floor, provid-
ed the enclosure is built in
compliance with applicable
requirements.
As used by the NFIP, an
"enclosure" is an area that
is enclosed on all sides by
walls.
The NFIP defines a "base-
ment" as any area that is
below -grade on all sides.
The regulations do not allow
basements to extend below
the BFE.
Owners of existing elevated
buildings with enclosures
below the BFE may wish
to retrofit the enclosures.
Lower NFIP flood insur-
ance rates may apply if the
retrofit enclosures have
openings that meet the re-
quirements in this Technical
Bulletin and also meet other
requirements for enclosures
(limited use, flood dam-
age- resistant materials, and
elevated utilities).
TECHNICAL BULLETIN 1 - AUGUST 2008
(including crawlspaces) are permitted if used only for parking of vehicles, building access,
and storage. Figure 1 illustrates a typical crawlspace foundation wall and a typical framed wall
surrounding an enclosed area.
If enclosure walls are not designed with openings to relieve the
pressure of standing or slow- moving water against them (called
hydrostatic loads), the walls can be damaged or fail during a
flood. If the walls are "load- bearing" walls that support the el-
evated building, failure of the walls may result in damage to,
or collapse of, the building. To address this concern, the NFIP
regulations require that enclosure walls contain openings that
will allow for the automatic entry and exit of floodwaters. These
openings allow floodwaters to reach equal levels on both sides
of the walls, thereby lessening the potential for damage caused
by a difference in hydrostatic loads on opposite sides of' the
walls. In A zones, the requirement for flood openings applies
to all enclosed areas below new elevated buildings and below
substantially improved buildings.
Areas of shallow flood-
ing may be shown as AO
zones on FIRMs. Rather
than BFEs, AO zones have
"flood depths" that range
from 1 to 3 feet. In these
zones, all NFIP require-
ments related to BFEs
apply, including elevation of
the lowest floor to or above
the designated flood depth
and requirements for enclo-
sures with flood openings
that are located so that
floodwaters will flow in and
out.
This Technical Bulletin explains the NFIP requirements for flood openings and provides
guidance for prescriptive (non - engineered) openings and engineered openings. Non -engi-
neered openings are used to meet the NFIP's prescriptive requirement of 1 square inch of net
open area for every square foot of enclosed area. As an alternative, engineered openings that
have characteristics that differ from non - engineered openings may be used provided they are
designed and certified by a registered design professional as meeting certain performance
characteristics described in this Technical Bulletin.
Joist(Truss
Framed wall
around enclosure
Solid perimeter —emu ( Crawlspace
foundation wall
(CMU or poured
concrete)
Flood opening
Flood opening
P g
No more than grade
No more than
1 foot
1 foot
Interior grade
JInterior
Exterior grade
Exterior grade
Footing depth per
building code
Figure 1. Typical enclosures with flood openings
TECHNICAL BULLETIN 1 - AUGUST 2008
This Technical Bulletin also discusses how openings could affect flood insurance premiums,
provides examples of enclosures that require openings and situations where openings are not
required, and outlines the requirements for, and provides guidance on, the following:
■ Installation of openings, including the minimum number of openings and height of open-
ings above grade,
■ Non - engineered openings, and
■ Engineered openings.
Examples are provided to illustrate types of buildings and enclosures that require openings,
and to address several commonly encountered situations. Other situations may require the ad-
vice of a registered design professional. Questions should be directed to the appropriate local
official, NFIP State Coordinating Office, or FENIA Regional Office.
Solid perimeter foundation walls and walls surrounding en-
closed areas below the BFE may be damaged by forces related
to moving floodwaters and wave impacts (called hydrodynamic
loads), and debris impacts. The requirement for openings is
intended to reduce only flood damage associated with hydro-
static — not hydrodynamic — loads.
Hydrodynamic loads and debris impacts may be significant in
some flood hazard areas shown as A zones on FIRNIs, includ-
ing riverine areas where high flow velocities are likelv (e.g.,
faster than 5 feet per second) and areas where wave heights of
1.5 feet or more are possible. In these areas, it is recommend-
ed that a registered design professional evaluate foundation
designs. Open foundations without enclosed areas are less vul-
nerable to the type of damage that can be caused by high flow
velocities and wave action.
This Technical Bulletin dis-
cusses openings in walls
below the BFE. Readers
should check with the
community to determine
whether a higher eleva-
tion standard is enforced.
For example, communi-
ties may add freeboard or
may regulate to the design
flood elevation (DFE). In
those cases, references to
the BFE in this Technical
Bulletin should be con-
strued as references to
the community's elevation
requirement.
Buildings in V zones (Zones V, 'VT-, and VI-V30) must meet certain design and construction
requirements that are specified in the NFIP regulations at Section 60.3(e). The area below the
lowest floors of buildings in V zones must be free of obstruction or, if enclosed, the walls of
enclosures must be constructed with non - supporting breakaway walls, open wood lattice -work,
or insect screening. Openings may be provided, but are not required, in breakaway walls un-
der buildings in V zones. For information on V -zone design and construction requirements,
refer to the NFIP regulations, the Technical Bulletin series (especially Technical Bulletin
5, Fiee-of- Obstruction. Requirements and Technical Bulletin 9, Design. and Construction Guidance
for Breakaway 11%alls Below Elevated Coastal Buildings), the Coastal Construction. Manual (FENEN
55CD), Flood Resistant Design and Construction (ASCE 24), and Home B2r.dder's Guide to Coastal
Construction (FEN1A 499).
TECHNICAL BULLETIN 1 - AUGUST 2008 3
NFIP Regulations
The NFIP regulations for enclosures are codified in Title 44 of the Code of Federal Regula-
tions, in Section 60.3(c) (b), which states that a community shall:
"Require, for all new construction and substantial improvements, that fully enclosed ar-
eas below the lowest floor that are usable solely for parking of vehicles, building access,
or storage in an area other than a basement and which are subject to flooding shall be
designed to automatically equalize hydrostatic flood forces on exterior walls by allowing
for the entry and exit of floodwaters. Designs for meeting this requirement must either be
certified by a registered professional engineer or architect or meet or exceed the following
minimum criteria: A minimum of two openings having a total net area of'not less than
one square inch for every square foot of enclosed area subject to flooding shall be provided.
The bottom of all openings shall be no higher than ore foot above grade. Openings may
be equipped with screens, louvers, valves, or other coverings or devices provided that they
permit the automatic entry and exit c f floodwaters. "
Proposals for substantial improvement of existing buildings in SFHAs, and proposals to repair
those that have sustained substantial damage, must comply with the requirements for new
construction. In A zones, the applicable requirements include openings in the walls surround-
ing enclosed areas below the BFE. As part of issuing permits, community officials must review
such proposals to determine whether they comply with the requirements. Further informa-
tion on substantial improvement and substantial damage is found in Answers to Questions About
Substantially Damaged Buildings (FEVIA 213).
The NFIP Technical Bulletins provide guidance on the minimum requirements of the NFIP regulations.
Community or State requirements that exceed those of the NFIP take precedence. Design profes-
sionals should contact the community to determine whether more restrictive provisions apply to the
building or site in question. All other applicable requirements of the State or local building codes must
also be met for buildings in flood hazard areas.
How Openings Affect Flood Insurance Rates
Careful attention to compliance with the NFIP regulations for flood openings is important
during design, plan review, construction, and inspection. Compliance influences both the
vulnerability to flood damage and the cost of NFIP flood insurance. If openings are not com-
pliant, the floor of the crawlspace or the floor of the enclosure becomes the `lowest floor." In
those cases, the result may be significantly higher flood insurance premiums, especially if the
floor of the crawlspace or enclosure is more than a foot or two below the BFE.
4 TECHNICAL BULLETIN 1 - AUGUST 2008
Documenting Elevations and Information About Openings
Communities are required to collect data from permittees to document the surveyed elevation
of the lowest floors of new buildings and existing buildings that are substantially improved.
Although the data may be provided in other formats, the NFIP's Elevation Certificate (FENLA,
Form 81 -31) is designed specifically for this purpose. The current version of the Elevation Cer-
tificate is online at http: / /xNi-,tiv.fema.gov /business /nfip /el-vinst.shtm.
The Elevation Certificate is designed to collect information that facilitates determining com-
pliance of new construction and to provide data necessary for the proper rating of NFIP flood
insurance. For guidance, see the instructions that accompany the Elevation Certificate and
the Floodplain. Afana.o-ement Bulletin: Elevation Certocate (FENIA 467 -1).
The Elevation Certificate has blanks that are to be completed if there are enclosures under
elevated buildings, including:
• The square footage of the enclosed area,
• The number of flood openings within 1.0 foot above adjacent grade, and
• The total net area of flood openings.
The Elevation Certificate provides space for comments. As noted above and explained in more
detail below, the regulations provide two ways to satisfi7 the requirements for openings. Com-
ments should be provided when engineered openings are used, and when there are other
aspects of enclosures and openings that comply with the requirements but that, without close
inspection, may appear to be non- compliant. The documentation required for engineered
openings should be attached to the Elevation Certificate (described on page 25, Documenta-
tion of engineered openings for flood insurance).
Enclosed Areas Below Elevated Buildings
The NFIP regulations specify that enclosed areas under elevated buildings may be allowed
provided the enclosed areas are used solely for:
■ Parking of vehicles (attached garages or parking areas be-
low elevated buildings)
■ Building access (stairwells, foyers, elevators)
■ Storage (low -value items)
Although crawlspaces are not listed explicitly as an allowable
use, buildings may be elevated using perimeter foundation
walls that create enclosed areas, typically called crawlspaces or
under -floor spaces. Crawlspaces provide access to under -floor
utilities such as pipes, ductwork, and electric conduits.
Some communities require
permittees to execute a
"non- conversion" agreement
to document their under-
standing that the use of
enclosures is limited, that
conversion to other uses is
not allowed, and that modi-
fication of enclosures may
result in higher NFIP flood
insurance rates.
TECHNICAL BULLETIN 1 - AUGUST 2008
It is important to understand how an otherwise compliant en-
closed area below the BEE can be rendered non - compliant by
installing features that are not consistent with the limitations
on uses. The following are not allowed below the BEE because
of potential damage and their presence is inconsistent with
the allowed uses: appliances, heating and cooling equipment,
plumbing fixtures, more than the minimum electric service
required to address life safety and electric code requirements
for building access and storage areas, and materials that are
not flood damage - resistant.
The only exception to the
openings requirement is
for non - residential build-
ings that are engineered to
be floodproofed by meeting
stringent requirements to
be watertight. For informa-
tion on floodproofing, refer
to Technical Bulletin 3, Non -
Residential Floodproofing
— Requirements and
Certification.
The NFIP regulations require that enclosed areas surrounded
by solid walls that extend below the BEE have flood open-
ings. The requirement applies whether the walls are load - bearing walls or non -load- bearing
walls. Therefore, openings are required in solid perimeter foundation walls that surround
crawlspaces and openings are required in the walls of fully enclosed areas that meet the use
limitations (parking of vehicles, building access, or storage). The requirement applies to new
construction and to buildings that are undergoing substantial improvement, including repair
of substantial damage.
Enclosures That Require Openings
Several examples of enclosures that require openings are described below:
• Solid perimeter foundation walls (crawlspaces or under -floor spaces)
• Solid perimeter foundation walls (below -grade crawlspaces)
• Solid perimeter foundation walls (with full- height under -floor spaces)
■ Garages attached to elevated buildings
■ Enclosed areas under buildings elevated on open foundations in A zones
• Enclosed areas with breakaway walls under buildings elevated on open foundations in A
zones
• Solid perimeter foundation walls on which manufactured hornes are installed
• Accessory structures (detached garages and storage sheds)
Solid perimeter foundation walls (crawlspaces or under -floor
spaces)
The crawlspace or under -floor space that is created when a
building is elevated on a solid perimeter foundation wall is an
enclosed area below the BEE that must meet all of the require-
ments for enclosed areas (refer to Figure l ). If a brick veneer,
siding, or other material covers the wall, then the openings
must completely penetrate into the enclosed area. A crawlspace
access with a door does not qualify as a flood opening unless
In many parts of the coun-
try, a common practice is
to build "conditioned crawl-
spaces" that are sealed and
have mechanical ventilation.
In SFHAs, all crawlspaces
must have flood openings
that meet the requirements
of the NFIP and the building
codes.
6 TECHNICAL BULLETIN 1 - AUGUST 2008
the door has an opening installed in it or otherwise meets the performance requirement that
it will allow autoinatic entry and exit of floodwaters.
As explained on page 14 (Height of Openings Above Grade), the bottom of each opening is
to be located no higher than 1 foot above the higher of the final interior or exterior grades
under the opening. Therefore, placement of the openings in the foundation wall requires
knowledge of the expected finished exterior grade and the final interior grade of the crawl -
space.
Building code requirements may call for ventilation of certain under-floor spaces. Ventilation
openings typically are positioned near the top of the foundation wall to facilitate air flow. In
most cases, ventilation openings will be too high above grade to satisfy the requirements for
flood openings.
Solid perimeter foundation walls (below -grade crawlspaces)
The NFIP regulations do not allow buildings to be constructed
with areas that are below grade on all sides (basements), ex- to are required
to adopt specific provi-
cept for certain engineered non - residential buildings that are sions in their ordinances
designed and certified to be floodproofed. Therefore, crawl- to be consistent with the
spaces that are below -grade on all sides are not allowed because limitations in TB 11 in or-
they are basements. An exception is available only in shallow der to permit below -grade
floodplains and then only if certain other requirements and crawlspaces.
limitations are met. Those requirements and limitations are
detailed in Technical Bulletin 11, Crawlspace Construction for Buildings Located in. Special Flood
Hazard areas: National Flood In-
surance Program. Interi.t Guidance.
According to this guidance, be-
low -grade crawlspaces may be
allowed provided the wall height
is less than 4 feet when measured
from bottom of the floor joist/
truss to the top of footing, which
must be no more than 2 feet be-
low -grade (see Figure 2). Flood
openings are required in the
foundation walls surrounding
these crawlspaces and, as noted
above, air ventilation may be re-
quired.
Although crawlspaces that satisfy
the limitations in TB 11 are not
considered basements for flood -
plain management purposes, it
is important to note that they
are basements for NFIP flood
Joist/ Truss
BFE —►
Flood opening —+
No more than
1 foot
4 -foot
maximum
Exterior grade 2 -foot
,._,.. �. maximum
F . ' '' t Interior grade
Figure 2. Limitations on below -grade crawlspaces in shallow
flood hazard areas (TB 11)
TECHNICAL BULLETIN 1 - AUGUST 2008 7
insurance purposes. Therefore, NFIP flood insurance will be more expensive if the grade inside
the crawlspace is below the exterior grade on all sides In addition, below -grade crawlspaces
may contribute to increased humidity and mold growth. TB 11 requires that an adequate
drainage system be provided in order to minimize floodwater contact with crawlspace materi-
als and related moisture damage.
Solid perimeter foundation walls (with full- height under -floor spaces)
In SFHAs where the BFE is more than 4 or a feet above grade, or where owners want enough
head room to allow for parking of vehicles and storage, solid perimeter foundation walls may
be used to create full- height under -floor spaces (see Figure 3). The walls surrounding the un-
der -floor space must meet all of the opening requirements.
It is important that full - height under -floor spaces also meet all other NFIP requirements to
minimize the likelihood of future conversion to uses other than the allowed uses (parking
of vehicles, building access, or storage). As noted in the discussion of limitations on uses of
enclosures, the following are not allowed below the BFE in full- height enclosures because of
potential damage and their presence is inconsistent with the allowed uses: appliances, heating
and cooling equipment, plumbing fixtures, more than the minimum electric service required
to address life safety and electric code requirements for building access and storage areas, and
materials that are not flood damage - resistant.
Figure 3. Full- height
solid perimeter walls
surrounding garage and
storage area (only two
openings visible)
Garages attached to elevated buildings
Many buildings, especially homes, are designed with attached garages. An attached garage
may have its floor below the BFE provided the garage meets all of the requirements for an en-
closed area below the BFE. The use of the garage space must be limited to parking of vehicles,
building access, and storage.
8 TECHNICAL BULLETIN 1 - AUGUST 2008
Openings are required in the exterior walls of the garage, and openings may be installed in
exit doors and garage doors (see Figure 4). It is important to note that garage doors them-
selves do not meet the requirements for openings. Human intervention would be necessary
to open garage doors when flooding is expected, which is inconsistent with the requirement
that openings allow for the automatic entry and exit of floodwaters. Similarly, gaps that may
be present between the garage door and the doorjamb or walls do not guarantee automatic
entry and exit of floodwaters and do not count towards the net open area requirement.
If an attached garage is built with its floor below the BFE and it does not have compliant
openings, the garage floor becomes the lowest floor. Flood insurance premiums may be sig-
nificantly higher than if the garage complies with the requirements for openings and other
requirements, such as flood damage- resistant materials and elevated utilities.
Figure 4. Attached
garage, with engineered
openings installed in the
garage door
Enclosed areas under buildings elevated on open foundations in A zones
• building that is elevated on an open foundation (e.g., piers, posts, columns, or pilings) in an
• zone may have enclosed areas below the elevated floor (see Figure 5). Sometimes only part
of the footprint is enclosed, such as for a stairwell or storage room. All of the requirements for
enclosed areas apply, including openings, elevated utilities, flood damage - resistant materials,
and limitations on use (parking of vehicles, bung access,
and storage).
Open foundations are recommended in riverine flood haz-
ard areas where flow velocities are expected to exceed 5 feet
per second because of the anticipated hydrodynamic loads
and potential for debris impact and scour. These loads may
be sufficient to damage typical solid perimeter foundation
walls, even though flood openings are provided.
ASCE 24 and several of
the fact sheets included in
the Home Builder's Guide
to Coastal Construction
(FEMA 499) are excellent
resources for flood- resistant
building methods in coastal
A hazard areas.
TECHNICAL BULLETIN 1 — AUGUST 2008 9
If a waterway was studied using detailed methods and a floodway is shown on a FIRM, then
the Floodway Data Table in the Flood Insurance Study should be reviewed for data that can
be used to estimate velocities. For each cross section, the table provides the mean velocity that
can be used to approximate velocities in the floodplain outside of the floodway. For other wa-
terways in areas known to have fast - moving water, standard methods can be used to compute
an approximate velocity. Examples of other sources of information that should be reviewed
include local observations and studies prepared by State and local agencies.
Figure 5. Enclosure with flood
openings, under house elevated on
pilings
Enclosed areas with breakaway walls under buildings elevated on open foundations in A zones
Open foundations are also recommended in A zones in coastal areas where breaking wave
heights can be between 1.5 and 3.0 feet (called Coastal A Zones). In these areas, it is recom-
mended that walls surrounding enclosed areas be designed as breakaway walls. Flood openings
are required in breakaway walls in A zones in order to comply with the NFIP requirements
ASCE 24 includes specific provisions for openings in breakaway walls.
Solid perimeter foundation walls on which manufactured homes are installed
Manufactured homes may be installed on solid perimeter foun-
dation walls that enclose space below the homes (see Figure 6) .
Even if it is not part of the load - bearing foundation, a solid
perimeter wall is required to have openings, otherwise hydro-
static loads may damage the perimeter wall, which could, in
turn, damage the home's supporting foundation and anchor
system.
Figure 7 shows an example of a framed enclosure below an ele-
vated manufactured home. In this case, the full- height enclosed
Openings are required in
rigid skirting that is attached
to frames or foundations of
manufactured homes to re-
lieve hydrostatic loads and
minimize transferring loads
that can damage homes
and their supporting foun-
dation systems.
10 TECHNICAL BULLETIN 1 - AUGUST 2008
area is used for parking and storage. Openings are required because the walls surrounding
the enclosed area are solid walls. As indicated by the driveway on the left, the interior slab is
higher than the exterior grade along the side of the building. The openings shall be located
within 1 foot of the interior grade.
Manufactured home
Ground anchors
not shown for
clarity
Masonry
perimeter wall
Pier
Flood opening
777 I- - - -� I - -i .�\
Figure 6. Manufactured home
supported on piers; masonry perimeter
wall with flood openings (ground
anchors not shown)
Figure 7. Manufactured
home installed above
a full- height framed
garage (note elevation
of driveway slab on left;
the openings are within
1 foot of interior grade of
the slab)
TECHNICAL BULLETIN 1 - AUGUST 2008
Accessory structures: detached garages and storage sheds
Detached garages and detached storage buildings in A zones may be permitted without requir-
ing them to be elevated if they comply with all of the requirements for enclosures. Garages
and other accessory buildings must be used only for parking of vehicles and storage, utilities
must be elevated, flood damage - resistant materials must be used below the BFE, the require-
ments for flood openings must be satisfied, and they must be anchored to resist flotation,
collapse, or lateral movement under flood conditions.
Communities are required to regulate all development in SFHAs, including the placement of
small storage sheds. Storage sheds in A zones are not required to be elevated if they comply
with all of the requirements for enclosures. They must be used only for storage, utilities must
be elevated, flood damage - resistant materials must be used below the BFE, and the require-
ments for flood openings must be satisfied. In addition, sheds are to be anchored to prevent
flotation, collapse, or lateral movement under flood conditions.
Situations That Do Not Require Openings
Two situations that do not require openings are described below:
• Manufactured home with skirting
• Back -filled stem wall foundation
Manufactured home with flexible skirting
Skirting used to enclose the area under manufactured homes
typically is made of weather - resistant material and extends
from the bottom of the home down to grade. Flexible skirt-
ing and rigid skirting that are not attached to the frame or
foundation of a manufactured home are not required to
have openings. However, where floodwaters are expected to
rise rapidly, there may be concerns about the skirting being
pushed against foundation systems. In these areas, open lat-
tice may be more appropriate to minimize the potential for
flood damage.
Filled stem wall foundation
A filled stem wall foundation (also called a chain wall) can
look like a solid perimeter foundation wall from the outside,
but this type of foundation is backfilled with compacted struc-
The National Fire Protection
Association's standard,
Model Manufactured Home
Installation Standard (NFPA
225), specifies that instal-
lation of skirting does not
trigger the requirement for
flood openings provided
the skirting does not pro-
vide structural support and
will collapse under wind and
water loads that are less
than those expected during
the base flood event without
causing structural damage
to the elevated home or the
foundation.
tural fill that supports the floor slab (see Figure 8). Because of the fill, unbalanced lateral
loads against the walls will be minimized as floodwaters, and thus openings are not required.
It is important that the final Elevation Certificate, or other documentation of elevations, in-
clude an explanation when stem wall foundations are used to avoid the assumption that it
is a crawlspace that lacks the required openings. The Elevation Certificate diagrams do not
illustrate filled stem wall foundations. A note in the comment section should describe the
foundation so that insurance agents are alerted as to why there are no openings.
12 TECHNICAL BULLETIN 1 - AUGUST 2008
Concrete slab
.. , Compacted select
4 ;o structural fill
.p � J
. o.
77
. 9 '
Exterior grade
Figure 8. Back - filled stem wall
foundation (openings not required)
Requirements and Guidance for Installation of Openings
The NFIP regulations specify certain installation requirements that must be met by all flood
openings, whether non - engineered openings or engineered openings, which are described
starting on page 18. The installation requirements address the minimum number of openings
and the maximum height of openings above grade. Additional guidance and explanations for
various situations are described below.
Minimum Number of Openings
Each enclosed area is required to have a minimum of two openings on exterior walls to allow
floodwaters to enter directly. In order to meet the requirement, the openings must be located
so that the portion of the opening intended to allow for inflow and outflow is below the BFE.
Openings that are entirely above the BFE (or any portion of an opening that is above the BFE)
will not serve the intended purpose during base flood conditions and thus are not counted
towards the compliance with the flood opening requirements.
The openings should be installed on at least two sides of each
enclosed area to decrease the chances that all openings could
be blocked with floating debris and to allow for more even
filling by floodwater and draining of the enclosed area. It is
recommended that openings be reasonably distributed around
the perimeter of the enclosed area unless there is clear justifi-
cation for putting all openings on just one or two sides (such
as in townhouses or buildings set into sloping sites).
The International
Residential Code® and the
International Building Code®
(by reference to ASCE 24)
both require a "minimum
of two openings on differ-
ent sides of each enclosed
area"
TECHNICAL BULLETIN 1 - AUGUST 2008 13
Figure 9 shows a sketch illustrating where openings could be located when an elevated build-
ing has multiple enclosed areas. [Note: the number of openings shown in Figure 9 is for
illustration only; the total number of openings and the adequacy of the net open area of those
openings depend on the type of opening, covering, and whether vent devices or engineered
openings are installed.]
Figure 9. Sketch of foundation plan of home with multiple enclosed areas, each with flood openings
(number of openings for illustration purposes only)
Height of Openings Above Grade
The bottom of each opening is to be located no higher than 1 foot above the grade that is
immediately tinder each opening. The purpose of this requirement is to satisfy the perfor-
mance expectation that the difference in water levels between the interior and exterior will
not exceed 1 foot as water begins to rise and as floodwaters recede from the site. Note that the
openings (or those portions that count towards the required net open area) must be located
below the BFE. In areas with shallow flood depths, this may require positioning the openings
closer to grade than the maximum I foot allowed.
Given the requirement that the bottom of openings shall not be higher than 1 foot above
grade, a question arises if the interior and exterior grades are different: which grade should
be used to determine placement of flood openings- The higher of the final interior grade
and the finished exterior grade that is immediately under each opening is used to make this
determination:
■ Finished exterior grade. Care should be taken when placing backfill, topsoil, and land-
scaping materials around the outside of enclosures, especially solid perimeter foundation
14 TECHNICAL BULLETIN 1 - AUGUST 2008
installed in garage door
walls. If the finished exterior grade is higher than the interior grade on all sides of the
building, then the enclosed area becomes a basement as defined by the NFIR
■ Final interior grade. The trench that is excavated to construct footings and foundation
walls must be backfilled completely, otherwise a basement is created. If the interior grade
is higher than the exterior grade, the openings are to be no higher than 1 -foot above the
interior grade.
Installation Examples
Interior grade higher than exterior grade
Consider a crawlspace enclosure that has its interior grade higher than the exterior grade. As
water rises against the outside of the foundation, the ground or fill on the interior balances
the hydrostatic load (see Figure 10). It is only when the water rises above the interior grade
that the lateral load becomes unbalanced and therefore must be equalized by openings.
When viewed from the outside, a solid perimeter foundation wall or wall surrounding an en-
closed area with the interior grade higher than the exterior grade will appear to not meet the
installation requirements for openings. The openings will appear to be too high above the ex-
terior grade (illustrated in Figure 7). Therefore, it is important that the final documentation
of as -built elevations note the difference in interior and exterior grades. For example, if the
NFIP Elevation Certificate is used, comments should explain that the intefior grade is higher
than the exterior grade and it should be noted whether the openings are (or are not) within
1 foot of the higher of the two grades.
Figure 10. Illustration of flood
openings installed within 1 foot of the
higher of interior or exterior grade
TECHNICAL BULLETIN 1 - AUGUST 2008 15
Sloping sites
Buildings on solid perimeter foundation walls that are set into a sloping site present another
special situation with respect to installation of openings. Careful attention must be paid to the
following:
■ The interior floor along the lower side of a building that is set into a sloping site must be
at or above the exterior grade across the entire length of that side of the building, other-
wise the enclosure becomes a basement.
■ The bottom of each opening shall be located no higher than 1 foot above the exterior or
interior grade immediately below the opening, whichever is higher (see Figure 11).
■ For openings to perform their intended function, sufficient open area must be below the
BEE.
Figure 11. Openings in enclosure
walls, sloping site
Elevated
lowest floor
jBFE ---- - -- -- -- --- - - - - -- --- i BFE
..� .�
Each opening
no more than
1 foot above grade Interior grade must be at or
above the exterior grade along
the entire length of the lowest
side to prevent being a basement
Townhouses with limited exterior walls
Townhouses are single - family dwelling units constructed in a group of three or more attached
units in which each unit extends from foundation to roof and with exterior walls on at least
two sides. Openings are required if townhouses in SFHAs are constructed with solid perimeter
foundation walls or with solid walls surrounding enclosed areas under the elevated portion of
the building.
Because the interior townhouse units have less linear exterior wall length than the end units,
it can be a challenge to meet all of the requirements, especially the requirement for adequate
net open area and the requirement that each enclosed area have openings. If openings can-
not be provided in at least two walls, the NFIP allows all openings to be installed in one wall.
16 TECHNICAL BULLETIN 1 - AUGUST 2008
Design of interior townhouse units can satisfy the guidance that openings should be on differ-
ent sides if the walls inside the enclosed area have openings to connect enclosed spaces from
front to back. Figure 12 shows suggested locations for openings. [Note: the number of open-
ings shown in Figure 12 is for illustration only; the total number of openings and the adequacy
of the net open area depend on the type of opening, covering, and whether a vent device is
installed in the openings.]
It may be even more challenging to provide adequate openings in enclosures under interior
townhouse units if the multi -unit building is set into a sloping site, in which case it may be ap-
propriate to consider using a filled stem wall foundation or an open foundation. Use of fill
across one side of elevated townhouses may create a similar complication.
Storage room Storage room Storage room
3
Garage Garage Garage
All stairs open
underneath
Fo y ' ' Fo er Foyer
1 3 4
iO Openings in garage door O3 Openings in interior wall /door
2O Openings in exterior wall ® Openings in exterior door
Figure 12. Illustration of suggested flood openings in enclosures under elevated townhouses (number of
openings for illustration purposes only)
Openings that extend above the BFE
Only those portions of openings that are below the BFE can be counted towards the required
net open area. Stacked vent devices may be installed or large- dimension openings may be pro-
vided (Figure 13). In both cases, if the BFE does not reach the top of the opening, only the
portion that is below the BFE will count as contributing to the required net open area. Simi-
larly, if the floor of a mechanical room is below the BFE (with elevated equipment inside) and
a louvered door provides ventilation, only the open portion of the louvered door that is below
the BFE will count towards the required net area of flood openings.
TECHNICAL BULLETIN 1 - AUGUST 2008 1
Figure 13. Stacked vents inserted in
large openings must be below the BFE
Depth of water 1 foot or less
Some FIRMS show mapped SFHAs where the depth of water will be 1 -foot deep or shallower.
Although the difference in water depth between the outside and inside of the enclosure tin-
der a building in these areas will not exceed 1 foot during the base flood, the NFIP regulations
require openings.
There are at least two solutions to this situation. The first is to elevate the floor of the enclo-
sure the necessary height so that it is at or above the BFE and there is no need for openings.
The second solution is to install openings, taking care to ensure that all of the necessary open
area is below the BFE (otherwise the openings will not function as intended). This can be ac-
complished by positioning the bottom of the openings at or very close to grade, rather than
the maximum of 1 foot above grade. In addition to complNing with the regulations, the walls
will not experience excessive differential hydrostatic pressure when floodwaters rise higher
than the BFE.
Non - Engineered Openings and Engineered Openings
The NFIP regulations identify alternatives to provide sufficient size and number of openings
to allow for the automatic entry and exit of floodwaters. This section describes how this level
of performance can be satisfied by use of:
■ Non - engineered openings (or covers and devices) that meet the prescriptive require-
ment to provide 1 square inch of net open area for each square foot of enclosed area (as
18 TECHNICAL BULLETIN 1 - AUGUST 2008
described below, a variety of options and devices can serve
as non - engineered openings).
■ Engineered openings (or covers and devices) that are
specifically designed and certified by a registered design
professional as meeting the required performance and
design requirements outlined below (and, if applicable,
the community's building code).
■ Engineered openings (or covers and devices) for which
an Evaluation Report has been issued by the Internation-
al Code Council (ICC) Evaluation Service, Inc. (ICC -ES),
a subsidiary of the International Code Council, Inc.
(http:/ !wvrtiv.iccs�tfe.org) .
The International
Residential Code® includes
both the prescriptive (non -
engineered) alternative and
the engineered openings
alternative.
The International Building
Code° also includes both
alternatives by reference to
ASCE 24.
The following requirements for installation apply regardless of whether engineered openings
or non - engineered openings are used to satisfy the NFIP requirements (also see page 13, Re-
quirements and Guidance for Installation of Openings):
■ Each enclosed area must have a minimum of two openings; if there are multiple enclosed
areas, each area must have openings in its exterior walls,
■ The bottom of each opening must be no more than 1 foot above the higher of the interior
or exterior grade immediately under the opening, and
■ Any screens, grates, grilles, fixed louvers, or other covers or devices must not block or im-
pede the automatic flow of floodwaters into and out of the enclosed area.
Unacceptable Measures
It is important to note that FENIq has determined that certain measures are not acceptable as
flood openings, including:
■ Standard foundation air ventilation devices that can be closed manually, because they do
not allow for the automatic entry and exit of floodwaters unless they are permanently dis-
abled in the open position.
■ Standard foundation air ventilation devices that have detachable solid covers that are in-
tended to be manually installed over the opening in cold weather, because they do not
allow for the automatic entry and exit of floodwaters when the cover is in place.
■ Standard foundation air ventilation devices that are designed to open and close based on
temperature (unless thev also are designed to allow for the automatic entry and exit of
floodwaters).
■ Windows below the BFE, because the automatic entry and exit of floodwaters cannot be
satisfied by the expectation that windows will break under rising floodwaters.
■ Garage doors without openings installed in them, because human intervention is required
to open the doors when flooding is expected. Gaps between the garage door and the door
jamb or walls do not count towards the net open area requirement.
■ Standard exterior doors without openings installed in them.
TECHNICAL BULLETIN 1 - AUGUST 2008 19
Non - Engineered Openings
Non - engineered openings are openings that are used to satisfy the prescriptive requirement
that calls for 1 square inch of net open area for each square foot of enclosed area. A wide va-
riety of options is available to satisfy the prescriptive requirements.
The term "net open area" refers to the permanently open area of a non - engineered opening.
The NFIP regulations indicate that flood openings may be equipped with coverings or deN71c-
es provided that they permit the automatic entry and exit of floodwaters. The measurement
of the net open area must take into consideration any coverings that have solid obstructions,
such as grilles, fixed louvers, or faceplates. Figure 14 shows a typical standard air vent faceplate
and measurements of the net open area.
Figure 14. Typical standard air vent
faceplate (this example provides 42
square inches of net open area)
16.7 inches -�
6.5 0
inches
X0.5 inch
Closure device disabled
in the open position
Manufacturers of devices intended for use as standard air vents typically indicate the number
of square inches that each device provides for air flow- (either stamped into the metal frame or
noted on the packaging). The same number should be used for the net open area calculation
when these devices are installed as non - engineered openings. However, in order to qualifi! as
flood openings that permit automatic entry and exit of floodwaters, openings must not have
solid covers that are installed during cold weather. Similarly, typical air vent devices that are
designed to be opened and closed manually must be disabled permanently in the open posi-
tion.
Insect screens that do not impede the entry and exit of floodwaters are allowed and do not
affect the determination of the net open area. Communities that administer the International
Building Code"' (IBC) or the International Residential Code' (IRC') should note the require-
ment to cover ventilation openings to keep animals and insects from entering. These codes
provide a list of acceptable covering materials. The commentaries that accompany those codes
note that some covering materials may reduce the gross open area of the vent by as much as
30 percent. In areas where floodwaters are expected to carry debris such as grass clippings and
leaves, it is notable that screens tend to clog (Figure 15). Local officials may determine that
additional openings are required to increase the likelihood that openings will perform as ex-
pected, even if some become clogged with debris.
20 TECHNICAL BULLETIN 1 - AUGUST 2008
Figure 15. Typical air
vent clogged by flood
debris
Examples of several commonly used non - engineered openings are described below and shown
in Figures 16 through 21:
■ Figures 16 and 17 show typical standard air ventilation devices that are intended for instal-
lation in crawlspace foundation walls. If installed as flood openings, they must be disabled
permanently in the open position to satisfy the requirement
for automatic entry and exit of floodwaters (note that the
device shown in Figure 17 is not compliant because it is not
disabled in the open position).
■ Figure 18 shows two examples where the builder provided
decorative treatment for open holes; in each case, only the
net open area is counted, and the area covered by the deco-
rative treatment is not counted.
■ Figure 19 shows a common practice for solid perimeter
foundation walls constructed of standard 16" x 8" concrete
masonry blocks. If a block is omitted as shown, the result-
ing void provides 128 square inches of net open area.
■ Figure 20 shows where standard blocks are turned sideways.
The voids in the blocks are measured to determine the net
open area.
■ Figure 21 shows a foundation in which a hole was created
when the concrete was poured; a wood frame covered with
screening is inserted in the hole. The framed void is mea-
sured to determine the net open area.
The IRC and IBC (through
reference to ASCE 24) re-
quire that flood openings
are to be not less than 3
inches in any direction in
the plane of the wall. This
requirement applies to the
hole in the wall, exclud-
ing any device that may be
inserted such as typical
foundation air vent device.
Communities usually re-
quire screens over voids
(open holes) that are creat-
ed in walls to serve as flood
openings, to limit the entry
of insects and rodents pro-
vided the screens do not
impede the inflow and out-
flow of floodwaters.
TECHNICAL BULLETIN 1 - AUGUST 2008 21
Grate Louver Grille
W'-
uuuuuU�b
o
Figure 16. Examples of typical air vents used as flood openings (net open area varies)
loll �• _ - ,
Figure 17. Although this standard air vent was intended as flood openings, it is not acceptable because it is not
disabled in the open position and does not allow automatic inflow and outflow of floodwaters.
22 TECHNICAL BULLETIN 1 — AUGUST 2008
----n 0
■
Figure 18. Decorative treatments using fixed louvers and brickwork (count the "net open area" or have
certified as engineered openings)
��—
Figure 19. Foundation
wall with omitted blocks
as flood openings (insect
screen not visible)
of <-
- -I
TECHNICAL BULLETIN 1 — AUGUST 2008 23
h '
Figure 20. Concrete block turned sideways (insect Figure 21. Wood frame with insect screen inserted in
screening shown) opening in poured concrete foundation wall
Engineered Openings
Openings that are designed and certified by a registered design professional as meeting the
performance required by the regulations are called "engineered openings." This section
describes certification and documentation requirements for engineered openings and the
specific design requirements.
Engineered openings with individual certification
For architectural or other reasons, building designers or owners may prefer to use unique
or individually designed openings or devices. In these cases, a registered design professional
must submit a certification. As a general rule, States require a designer to be licensed to prac-
tice in the State in which building is located.
The original certification of the engineered openings must include the design professional's
name, title, address, signature, type of license, license number, the State in which the license
was issued, and the signature and applied seal of the certifying registered design professional.
The certification shall identify the building in which the engineered openings will be in-
stalled. The language of the certification shall address the following:
■ A statement certifying that the openings are designed to automatically equalize hydrostat-
ic flood loads on exterior walls by allowing the automatic entry and exit of floodwaters in
accordance with the Engineered openings, design requirements on page 26,
■ Description of the range of flood characteristics tested or computed for which the certifi-
cation is valid, such as rates of rise and fall of floodwaters, and
■ Description of the installation requirements or limitations that, if not followed, will void
the certification.
24 TECHNICAL BULLETIN 1 - AUGUST 2008
Engineered openings with ICC -ES Evaluation Reports
Engineered openings or devices may be accepted by local
officials as an alternative to non- engineered openings (pre-
scriptive) provided the designs are certified. The certification
may take the form of the individual certification described
above, or it can be an Evaluation Report issued by the ICC-ES.
The ICC-ES issues such reports for a variety of building prod-
ucts, methods, and materials. Evaluation Reports are issued
only after the ICC-ES performs technical evaluations of docu-
mentation submitted by a manufacturer, including technical
design reports, certifications, and testing that demonstrate
code compliance and performance.
Evaluation Reports are supported by certifications that in-
clude appropriate language describing performance of the
openings and the name, title, address, type of license, license
number, the State in which the license was issued, and the sig-
nature and seal of the certifying registered design professional.
The specific provisions that are addressed in the certification
mast include:
ICC -ES has issued
Acceptance Criteria for
Automatic Foundation Flood
Vents (AC364) for one type
of engineered opening. The
ICC -ES will develop ac-
ceptance criteria for other
types, upon request.
Local officials in communi-
ties that do not administer
the International Code
Series determine whether
to accept building prod-
ucts that have received
Evaluation Reports issued
by the [CC-ES.
■ A statement certifying that the openings are designed to automatically equalize hydrostat-
ic flood loads on exterior walls by allowing the automatic entry and exit of floodwaters in
accordance with the Engineered openings, design requirements below,
■ Description of the range of flood characteristics tested or computed for which the certifi-
cation is valid, such as rates of rise and fall of floodwaters, and
■ Description of the installation requirements or limitations that, if not followed, will void
the certification.
Documentation of engineered openings for compliance
An important part of the evidence necessary to document compliance is the certification of
engineered openings or the Evaluation Report. A copy of the individual certification or the
Evaluation Report is required to be kept in the community's permanent permit files, along
with inspection reports. The documentation can be submitted as part of the permit applica-
tion and design drawings, or submitted separately. Owners should retain the certification or a
copy of the Evaluation Report to submit along with applications for NFIP flood insurance.
Documentation of engineered openings for flood insurance
Insurance agents will request that property owners provide documentation as part of appli-
cations for NFIP flood insurance. The documentation should be attached to the Elevation
Certificate. The following are acceptable forms of documentation:
■ For engineered openings with individual certification, the certification described above
that is signed and sealed by a registered design professional who is licensed in the State
where the building in which the engineered openings are used is located; or
TECHNICAL BULLETIN 1 - AUGUST 2008 25
■ For engineered openings with ICC -ES Evaluation Reports, a copy of the Evaluation Report
that documents that the engineered openings meet the performance requirements of the
NFIP and the building code, and that specifies the number of such openings that are re-
quired for a specified square footage of enclosed area below the BEE; or
■ For engineered openings with ICC-ES Evaluation Reports, a letter or other written evi-
dence from the local official that use of engineered openings in a specific building is
acceptable.
Engineered openings, design requirements
The American Society of Civil Engineers (ASCE) developed the standard Flood Resistant Design
and Construction (ASCE 24). This standard applies to buildings and site developments pro-
posed in flood hazard areas; it is referenced by the International Building Code. ASCE 24 Section
2.6.2.2 contains installation and design criteria for engineered openings. ASCE 24 provides
the equation below to determine the total net area of engineered openings that are installed
in foundation walls or enclosure walls. The equation includes a coefficient that corresponds
to a factor of safety of 5, which is consistent with design practices related to protection of life
and property. This factor of safety also helps to account for the likelihood that insect screens
may clog with flood -borne debris. The ASCE 24 commentary provides additional background
on the derivation of the equation.
As with non- engineered openings, engineered openings must be designed to allow automatic
entry and exit of floodwaters.
Three design and performance criteria for engineered openings are specified in ASCE 24 but
are not explicitly identified in the NFIP regulations:
• Engineered openings are to perform such that difference between the exterior and inte-
rior water levels shall not exceed 1 foot during base flood conditions.
• Engineered openings are to be not less than 3 inches in any direction in the plane of the
wall. This requirement applies to the hole in the wall, excluding any screen, grate, grille,
louvers, or devices that may be placed in or over the opening.
• In the absence of reliable data on the rates of rise and fall, engineered openings are to be
designed based on the assumption that the minimum rate of rise and fall will be 5 feet per
hour. Where data or analyses indicate more rapid rates of rise and fall, the required num-
ber of openings is to be increased to account for those different conditions. The number
or size of the openings may be decreased if data or analyses indicate rates of rise and fall
are less than 5 feet per hour.
26 TECHNICAL BULLETIN 1 - AUGUST 2008
From ASCE 24, the equation to determine area of engineered openings:
A o = 0.033 [ 1 /C] R A
Where: A = total net area of openings required (in
0.033 = coefficient corresponding to a factor of safety of 5.0 (in • hr /ft
c = opening coefficient (non - dimensional; see ASCE 24,Table 2 -2)
R = worst case rate of rise and fall (ft/hr)
A = total enclosed area (ft
[ASCE 24] Table 2 -2
Flood Opening Coefficient of Discharge
Opening Shape and Condition
C
circular, unobstructed during design flood
0.60
rectangular, long axis horizontal, short axis
0.40a
vertical, unobstructed during design flood
square, unobstructed during design flood
0.35
rectangular, short axis horizontal, long axis
0.25b
vertical, unobstructed during design flood
other shapes, unobstructed during design flood
0.30
Notes:
a. When the horizontal dimension is twice or more the vertical dimension, use
0.4; as the dimensions approach a square, interpolate from 0.4 to 0.35.
b. When the horizontal dimension is half or less the vertical dimension, use 0.25;
as the dimensions approach a square, interpolate from 0.25 to 0.35.
Used with permission from ASCE.
TECHNICAL BULLETIN 1 - AUGUST 2008 27
The NFIP
The U.S. Congress established the NFIP with the passage of the National Flood Insurance
Act of 1968. The NFIP is a Federal program enabling property owners in participating com-
munities to purchase insurance as protection against flood losses, in exchange for State and
community floodplain management regulations that reduce future flood damages. Participa-
tion in the NFIP is based on an agreement between coin munities and the Federal Government.
If a community adopts and enforces adequate floodplain management regulations, FEMA will
make flood insurance available within the community.
Title 44 of the U.S Code of Federal Regulations contains the NFIP criteria for floodplain man-
agement, including design and construction standards for new and substantially improved
buildings located in SFHAs identified on the NFIP's Flood hisurance Rate Maps. FEMA en-
courages communities to adopt floodplain management regulations that exceed the NFIP
criteria. As an insurance alternative to disaster assistance, the NFIP reduces the escalating
costs of repairing damage to buildings and their contents caused by floods.
NFIP Technical Bulletins
This is one of a series of Technical Bulletins that FEMA has produced to provide guidance
concerning the building performance requirements of the NFIP. These requirements are con-
tained in Title 44 of the U.S. Code of Federal Regulations at Section 60.3. The bulletins are
intended for use by State and local officials responsible for interpreting and enforcing the re-
quirements in their floodplain management regulations and building codes, and by members
of the development community, such as design professionals and builders. New bulletins, as
well as updates of existing bulletins, are issued periodically, as necessary. The bulletins do not
create regulations; rather, they provide specific guidance for complying with the requirements
of existing NFIP regulations. Users of the Technical Bulletins who need additional guidance
should contact their NFIP State Coordinator or the appropriate FEMA regional office. The
User's Guide to Technical Bulletins (http: / /www.feina.gov /pdf /final /gtride0l.pdf) lists the bul-
letins issued to date.
Ordering Technical Bulletins
The quickest and easiest way to acquire copies of FEMA's Technical Bulletins is to down-
load them from the FEND website (http: / /wiv7Nv.fema.gov/ plan /prevent /floodplain /techbul.
shun).
Technical Bulletins also may be ordered free of charge from the FENLA, Publications Ware-
house by calling 1- 800 - 480 -2520, or by faxing a request to 301- 362 -5355, Monday through
Friday between 8 a.m. and 5 p.m. EST. Please provide the FEND publication number, title,
and quantity of each publication requested, along with your name, address, zip code, and dav-
time telephone number. Written requests may be also be submitted by mail to the following
address:
28 TECHNICAL BULLETIN 1 - AUGUST 2008
FELLA Publications
P.O. Box 2012
Jessup, AID 20794
Further Information
The following sources provide further information concerning openings in foundation walls
and walls of enclosures.
American Societ of Civil Engineers, Structural Engineering Institute. 2005. Flood Resistant De-
sign and Construction, ASCE /SEI 24-05.
American Society of Civil Engineers, Structural Engineering Institute. 2005. Rlinimum Design
Loads for Buildings and Other Structures, ASCE /SEI 7 -05.
FEMA. 1991. Answers to Questions About Substantially Damaged Buildings, FEMA 213.
FENLA. 2000. Coastal Construction Alanual, FEMA 55CD (3rd edition).
FEMA. 2004. Floodplain Management Bulletin: Elevation Certificate, FEMA 467 -1 (http: / /www.
fema.gov /pdf /fima /fema467- 6- 10- 04.pdt) .
FENIA. 2005. Home Builder's Guide to Coastal Construction: Technical Fact Sheet Series, FEMA 499.
FEMA. 2006. Elevation Certificate (FEXIA Form 81 -31, http: / /www.fema.gov /pdf /nfip /elvicert.
shtm).
ICC Evaluation Service, Inc. 2007. Acceptance Criteria for AutomaticFou.n.dation Flood V' nts (AC364,
http: / /w es.org /criteria /pdf files/ ac364.pdf).
International Code Council, Inc. 2006. International Building Code, IBC 2006.
International Code Council, Inc. 2006. International Residential Code, IRC` 2006.
National Fire Protection Association. 2005. Model Alan ifactured Home Installation. Standardd
NFPAA 225.
National Fire Protection Association. 2006. Building Construction and Safety Code', NFPA 5000.
TECHNICAL BULLETIN 1 - AUGUST 2008 29
Glossary
Accessory structure - A structure that is on the same parcel of property as a principal struc-
ture, the use of which is incidental to the use of the principal structure.
Base ood - The flood haying a 1- percent chance of being equaled or exceeded in any given
year, commonly referred to as the "100 -year flood." The base flood is the national standard
used by the NFIP and all Federal agencies for the purposes of requiring the purchase of flood
insurance and regulating new development.
Base ood elevation (BFE) - The height of the base (1- percent annual chance or 100 -year)
flood in relation to a specified datum, usually the National Geodetic Vertical Datum of 1929
(NGVD), or the North American Vertical Daturn of 1983 (NAVD).
Basement - Any area of a building haying its floor subgrade (below ground level) on all
sides.
Elevation certi Cate - A form developed by FENLA, to collect surveyed elevations and other
information about a building that is necessary to obtain flood insurance.
Enclosure or enclosed area - Areas created by a crawlspace or solid walls that frilly enclose
areas below the BFE.
Federal Emergency Management Agency (FEMA) - The Federal agency that, in addition to
carrying out other activities, administers the National Flood Insurance Program.
Flood Insurance Rate Map (FIRM) - The official map of a community on which FENLV has
delineated both the special flood hazard areas (SFHAs) and the risk premium zones applica-
ble to the community.
Hydrodynamic load - The load imposed on an immersed object, such as a foundation element
or enclosure wall, by water flowing against and around it. The magnitude of the hydrodynam-
ic load varies as a function of velocity and other factors.
Hydrostatic load - The load imposed on an immersed object such as an enclosure wall, by
standing or slowly moving water. The magnitude of the hydrostatic load increases linearly with
water depth.
Lowest oor -The lowest floor of the lowest enclosed area of a building, including a basement.
Any NFIP- compliant unfinished or flood - resistant enclosure usable used solely for parking of
vehicles, building access, or storage (in an area other than a basement) is not considered a
bui'lding's lowest floor, provided the enclosure does not render the structure in violation of
the applicable design requirements of the NFIP.
Mitigation Directorate - The component of FENLV directly responsible for administering the
flood hazard identification and floodplain management aspects of the NFIP.
30 TECHNICAL BULLETIN 1 - AUGUST 2008
Net open area - The permanently open area of a non - engineered opening intended to pro-
vide automatic entry and exit of floodwaters.
Opening, engineered - An engineered opening is an opening that is designed and certified
by a registered design professional as meeting certain performance characteristics related to
providing automatic entry and exit of floodwaters, the certification requirement may be satis-
fied by an individual certification or issuance of an Evaluation Report by the ICC Evaluation
Service, Inc.
Opening, non - engineered - A non- engineered opening is an opening that is used to meet
the NFIP's prescriptive requirement of 1 square inch of net open area for every square foot of
enclosed area.
Registered Design Professional - An individual who is registered or licensed to practice their
respective design profession as defined by the statutory requirements of the professional reg-
istration laws of the State or jurisdiction in which the project is to be constructed.
Special Flood Hazard Area (SFHA) - An area delineated on a FIRM as being subject to in-
undation by the base flood and designated as Zone A, AE, Al .A30, AR, AO, AH, A99, V, VE,
or VI -V30.
Substantial damage - Damage of any origin sustained by a structure whereby the cost of re-
storing the structure to its before - damaged condition would equal or exceed 50 percent of
the market value of the structure before the damage occurred. Structures that are determined
to be substantially damaged are considered to be substantial improvements, regardless of the
actual repair work performed.
Substantial improvement - Any reconstruction, rehabilitation, addition, or other improve-
ment of a structure, the cost of which equals or exceeds 50 percent of the market value of
the structure (or smaller percentage if established by the community) before the "start of
construction" of the improvement. This term includes structures that have incurred "substan-
tial damage," regardless of the actual repair work performed.
TECHNICAL BULLETIN 1 - AUGUST 2008 31