Controls Upgrade Proposal
Chiller Plant, AHUs, and VAV Boxes
Murray Nelson Government Center
September 22, 2025
Contents
Scope Summary .......................................................................................................................................... 2
Equipment Controlled: ................................................................................................................................ 2
Proposed Sequences: ................................................................................................................................... 3
Labor Summary .......................................................................................................................................... 5
Control Points List ...................................................................................................................................... 6
Pricing Breakout: ........................................................................................................................................ 9
Clarifications ............................................................................................................................................. 11
Exclusions ................................................................................................................................................. 11
Agreement ................................................................................................................................................. 12
Siemens Industry, Inc.
942
Scope Summary
Siemens Industry, I is pleased to provide the following turnkey proposal to upgrade
the controls for the Chiller Plant, AHUs, and the VAV Boxes in the Murray Nelson Government Center
in Key Largo, Florida.
The following is a summary of the proposed controls upgrade:
a) New APOGEE Controllers for the Chiller Plant, AHUs, and the VAVs.
b) Like-for-like control points replacement.
c) Existing analog sensors, actuators, and end-devices shall be replaced with new.
d) The existing AHU chilled water control valves and control dampers are assumed to be in good
working condition and shall be reused.
e) Includes setting up critical alarms for 24/7/365 System Performance Monitoring service.
f) Includes updating the existing Fault Detection and Diagnostics service with new point names.
g) Includes travel and per diem.
Equipment Controlled:
AHUs (4)
nd
o 1 Meeting Room / Auditorium (located in 2 floor mechanical room)
o 2 Lobby (located in attic)
nd
o 3 Offices (located in 2 floor mechanical room)
o 6 Offices (located in attic)
Zone Dampers (3) for AHU-1
o Control Room
o Front Seating / Stage (BOCC Platform) with Electric Reheat
o Rear Seating
VAV Boxes (38) for AHUs 3 and 6
o (30) With Electric Reheat
o (8) Cooling Only
Exhaust Fan (1)
o Toilets
Chiller Plant
o Air Cooled Chiller (in old cooling tower location)
o (2) Pumps
Siemens Industry, Inc. Page 2 of 12
943
Proposed Sequences:
AHU-1 Multi-Zone (Meeting Room / Auditorium):
o Control of chilled water control valve to maintain supply air setpoint of 55 degrees (user
definable).
o Supply air temperature reset up to 58 degrees on cooler days if outside air is below 60
degrees (user adjustable).
o Outside air damper shall modulate to maintain return air C02 setpoint (user definable)
during occupied schedules. Minimum outside position (user definable) shall be set
during occupied schedules. During unoccupied schedules outside air damper shall be
closed.
o Setup of Meeting Room occupancy schedule. During meeting occupied modes, supply
air temperature reset down to 52 degrees if Boardroom thermostats (1-3 Front Seating /
Stage and 1-1 Rear Seating) are unable to reach setpoint at max zone damper cooling
position (i.e. room to warm).
o On a rise above the return air humidity setpoint (user definable), the chilled water valve
shall open, and the Zone Damper #3 (Front Seating / Stage) electric reheat shall
modulate up to 50% (user definable) to control space temperature setpoint.
o Setup of occupied and unoccupied building time of day schedules. During unoccupied
times outside air damper shall be closed and exhaust fan shall be commanded off.
AHU-2 Constant Volume (Lobby):
o In cooling mode, control of chilled water control valve to maintain return air setpoint
(user definable).
o In heating mode, electric reheat shall be staged to maintain return air temperature
setpoint (user definable).
o Outside air damper shall modulate to maintain return air C02 setpoint (user definable)
during occupied schedules. Minimum outside position (user definable) shall be set
during occupied schedules. During unoccupied schedules outside air damper shall be
closed.
o On a rise above the return air humidity setpoint (user definable), the chilled water valve
st
shall open, and the 1 stage of electric reheat shall stage to control return air temp
setpoint (user definable).
o Setup of occupied and unoccupied building time of day schedules. During unoccupied
times outside air damper shall be closed and exhaust fan shall be commanded off.
AHU-3 and AHU-6 Variable Volume (Offices):
o Control of chilled water control valve to maintain supply air setpoint of 55 degrees (user
definable).
o Supply air temperature reset up to 58 degrees on cooler days if outside air is below 60
degrees (user adjustable).
o Control of speed of VFD to maintain duct static pressure setpoint (user definable).
o Setup of occupied and unoccupied building time of day schedules. During unoccupied
times outside air damper shall be closed and exhaust fan shall be commanded off.
VAVs Cooling Only:
o Box damper positions shall be modulated between minimum and maximum CFM
setpoints to maintain room temperature setpoint (adjustable at thermostat).
o Night (unoccupied) settings.
Siemens Industry, Inc. Page 3 of 12
944
VAVs Electric Reheat:
o In Cooling Mode:
On rising temperature, damper modulates from minimum position to maximum
cooling. Reheat is OFF. Cooling airflow setpoint varies from min to max.
On falling space temperature, damper modulates from maximum to minimum
position. Reheat remains OFF. Airflow reduces to minimum setpoint
o In Heating Mode, on continued falling temperature (below heating setpoint), damper
maintains minimum airflow position. Electric reheat stages on in sequence. Airflow
increases to heating airflow setpoint.
o Night (unoccupied) settings.
Zone Dampers:
o Zone damper positions shall be modulated to maintain room temperature setpoint
(adjustable at thermostat). Space humidity sensors are for monitoring only.
o Night (unoccupied) settings.
Siemens Industry, Inc. Page 4 of 12
945
Labor Summary
1. Labor to provide Siemens standard submittals / record documents:
o System architecture (Siemens BACnet/IP & MS/TP)
o Network address schedule
o System flow diagrams
o Control installation / wiring diagrams
o Control & Component Panel layouts
o Equipment / Instrumentation datasheets
o Point database
o Sequences
2. Labor to provide controls installation
o Work during normal business hours.
o Programming
o Map new controllers and points to existing Desigo CC EBMS.
o Includes updates to existing Desigo CC EBMS graphics
o Work during normal business hours.
3. Labor to provide Siemens standard startup & checkout:
o Point database verification
o Point-to-point
o Sequence verification
4. Labor to provide Siemens project management, to include the following:
o BMS project scope only and associated meetings and coordination as required by
project schedule (not full-time on-site superintendent or project manager)
o Project meetings attendance
o Project documentation requirements
o Coordination with installation team
o Subcontractor management (if required)
o Material ordering and delivery coordination
o Project turnover documentation support
5. Labor to provide 8 hours of owner training
6. One-year parts and labor warranty on new controls upon beneficial use of systems.
Siemens Industry, Inc. Page 5 of 12
946
Control Points List
AHU 1 and Zone Dampers
AHU 2
Siemens Industry, Inc. Page 6 of 12
947
AHU 3
AHU 6
VAVs Cooling Only (Qty 8)
VAVs With Electric Reheat (Qty 30)
Siemens Industry, Inc. Page 7 of 12
948
Chiller Plant
Siemens Industry, Inc. Page 8 of 12
949
Pricing Breakout:
Siemens Industry, Inc. Page 9 of 12
94:
Siemens Industry, Inc. Page 10 of 12
951
Clarifications
Existing main controller enclosures and 120V power shall be reused.
It is assumed that VAV boxes are accessible above the ceiling.
VAV box cooling and heating min/max CFM settings shall be obtained from drawings and
existing control system setpoints.
Existing thermostat locations shall be reused.
Work during normal business hours.
Existing AHUs and Plants control wiring is assumed to be in good condition and shall be
reused.
Existing control enclosures shall be reused.
AHU chilled water control valves and actuators are assumed to be in good working condition
and shall be reused.
AHU control and zone dampers are assumed to be in good working condition and shall be
reused. New actuators shall be provided.
It is assumed that AHUs 4 and 5 do not exist.
It is assumed that AHU and FCU valves are 3-way and chilled water pumping system is
constant volume.
Exclusions
The following are the exclusions to the Controls Upgrade Proposal:
Relocation of furniture, computers, etc. for access to VAVs in ceiling.
Repairs to existing control wiring.
Repairs to AHU mechanical and electrical equipment.
Repairs to VAV boxes and zone dampers.
Repairs to AHU VFDs.
Repairs to AHU control dampers and control valves.
New main (AHU and Plant) controller enclosures.
Controls for FCU in mechanical room.
Test and balance.
Third-party commissioning.
Overtime labor.
Ethernet drops and configuration.
Personal computer hardware and operating system software.
Patching and painting (if required).
Fire alarm system testing and/or shutdown modifications.
Changes to system required by Inspector to meet current codes.
Controls for FCU-8 in Elevator Room. Assumed to be controlled by standalone thermostat.
Asbestos abatement, and work within asbestos areas.
Bond.
Permit.
Per project aggregate insurance.
Siemens Industry, Inc. Page 11 of 12
952
Agreement
Controls UpgradeProposal
Chiller Plant, AHUs, and VAV Boxes
Murray NelsonGovernment Center
By and Between:
Monroe County FloridaSiemens Industry, Inc.
1100 Simonton Street3021 N. Commerce Parkway
Key West, FL 33040Miramar, FL 33025
Siemens Industry, Inc. shall provide the services as outlined in the attached proposal dated 09/22/25.
Services shall be provided at the Murray NelsonGovernment Center in Key Largo,Florida.
Controls UpgradeInvestment:$249,245.53
Prices quoted are firm for 30days.
25% mobilization due upon receipt of order. Progress payments thereafter.
Net 30payment terms.
TheTerms and Conditions of thisproposal are those in the Master Agreement between Monroe
County, Florida and Siemens Industry, Inc., and are considered part of the proposal.
Siemens reserves the right to adjust prices to reflect the impact of any new or modified taxes, duties,
tariffs, or equivalent measures, whether direct or indirect, imposed by any U.S. or foreign
governmental authority that are applicable to our offering, including any hardware, software, or
service components contained therein.
Proposal accepted by:Proposal submitted by:
Name:William DeSantisName:Bradley L. Ayres
Title:DirectorFacilities MainenanceTitle:Account Executive
Monroe County FloridaSiemens Industry, Inc.
Purchase Order #: _________________
__________________________________________________________________
SignatureSignature
Date:___________________________Date:09/22/25
Siemens Industry, Inc.Page 12of12