Ordinance 021-1983ORDINANCE NO. 021 -1983
AN ORDINANCE OF THE COUNTY OF MONROE, FLORIDA,
PROVIDING THAT THE CODE OF ORDINANCES OF MONROE
COUNTY, FLORIDA, BE AMENDED BY REVISING CHAPTER
6, BUILDINGS AND CONSTRUCTION, OF SAID CODE;
REFLECTING CHANGES IN THE LATEST SUPPLEMENT TO
THE NATIONAL ELECTRICAL CODE; PROVIDING FOR
SEVERABILITY; PROVIDING FOR INCLUSION IN THE
CODE OF ORDINANCES OF MONROE COUNTY, FLORIDA;
AND PROVIDING FOR AN EFFECTIVE DATE.
BE IT ORDAINED BY THE BOARD OF COUNTY COMMISSIONERS OF MONROE
COUNTY, FLORIDA:
Section 1. That Section 6-110 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-110. Wall switches for lights required in
certain instances.
All lights installed or used within six (6) feet
of basins, sinks, toilets or bath tubs, or in any
room which has a floor which is permanently damp,
or which are installed or used in any location where
a person operating the same might come in contact
with any grounded objects, such as gas or water
pipes or other grounded metal work, shall be controlled
by a wall switch. A convenience outlet shall be
installed in all residential bathrooms and is to be
connected to a ground fault system."
Section 2. That Section 6-125 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-125. Application for permit.
Before any electrical wiring or electrical apparatus
or equipment for light, heat or power shall be
installed, within or attached to any building or
structure, either public or private within the limits
of the County, a written application for a permit
to do so must be made to the County BUILDING OFFICIAL.
The application shall be accompanied by a complete
set of plans and specifications completely describing
all proposed electrical work. Plans must show size
of main service in amperes, wire size and type,
conduit size, all sub -feeds in amperes, type and
size wire and size of conduit, type panels,
disconnects. The location of services and their
disconnects, location of distribution centers with
a panel schedule of all circuits, list all special
purpose outlets and fixed appliance circuits as may
be necessary in the opinion of the County BUILDING
OFFICIAL to determine whether the installation as
described will be in conformity with the require-
ments of this regulation. If it shall be found
by the County BUILDING OFFICIAL that the installation
as described will conform with the requirements of
this regulation, and if the applicant has complied
with all the provisions of this regulation, a
permit for such installation shall be issued by the
said County BUILDING OFFICIAL. The permit when
issued shall be for such installation as is described
in the application. An application for the service
location, approved by the Power Company must be
submitted when making application for permit."
Section 3. That Section 6-134 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-134. Rough -in inspection procedure.
For an electrical rough -in inspection, all plumbing,
framing and duct work must be inspected and passed.
No concealed work to be covered with any materials
before all inspections are passed. "only the electrical
contractor or his authorized foreman can call for
inspections." In the case of home owner doing his own
wiring, only he can call for inspections. For rough -
in inspection, all tubing or romex must be complete
wiring system with all wires pulled, joints made and
taped or scotch locks, mud rings on, pipe strapped
where necessary. There must be a minimum of six (6)
inches of free wire for all boxes that there will be
devices in, all ground wires to be made up and connected
in metal boxes per NEC 250-114(a). Work that does not
pass inspection the first time, there is a $30.00 re -
inspection fee, which is to be paid at the office of
the Building Inspection Department. When the fee is
paid and violations corrected, call for re -inspection."
Section 4. That Section 6-136 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-136. Issuance of certificate.
When electrical wiring, apparatus or fixtures
covered by a permit shall be found on inspection
by the County BUILDING OFFICIAL to conform to the
rules and regulations provided by this regulation,
the County BUILDING OFFICIAL shall issue a final
Certificate of Inspection certifying that the wiring,
apparatus or fixtures have been inspected and found
to comply with the terms of this regulation, but no
such Certificate shall be issued until such equipment
is made to conform to such rules and regulations.
Section 5. That Section 6-150 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Section 6-150. Main service disconnects. A single
service fused disconnect or circuit breaker of a
minimum of one hundred (100) AMP capacity shall be
required in residential buildings of six hundred (600)
square feet or more, located in a readily accessible
place as near the point of entrance as may be possible,
considering the character of the building and accessi-
bility in case of fires or other reasons for opening
the service disconnecting the premises from feeder
mains, unless outside of building per NEC Section 230-
44, then the main breaker in the distribution panel
may serve as the main disconnect.
Service fused disconnect or circuit breaker protection
at the meter location in a single family or duplex
residences will not be required if all of the following
conditions are met:
(a) The distance from the meter to the main service
protection disconnect is 20'-0 or under.
(b) The area where the service raceway is run is
open under the building. If the area is enclosed,
then a service fused disconnect or circuit breaker
will be required or the raceway encased in minimum
two (2) inches concrete.
The height of the main switch or breaker shall not
be higher than seven (7) feet or less than four (4)
feet from the ground or floor. Where more than one
(1) main switch, they must be grouped in same location
and readily accessible, plainly marked "Main #1,
Main #2, etc...." The minimum service for buildings
under 600 square feet when indicated load does not
exceed 5,000 watts based on 200 watts per 115 volt
current consuming outlets, plus maximum wattage for
special purpose outlets, plus actual main pull wattage
for direct connected loads, shall be 70 AMP and the
service conductors shall not be less than three (3)
#4 wires. The height of the main switch or breaker
shall not be higher than seven (7) feet or less than
four (4) feet from the ground or floor. When a main
service entrance serves more than six (6) meters, a
main service disconnect shall precede the meters.
All service equipment to be above 100 year flood stage,
or as approved by the local utility company. No split -
buss or parallel panels to be used (except in some
commercial work with permission of inspection department)."
Section 6. That Subsection (b) of Section 6-151 of Chapter 6,
Buildings and Construction, of the Code of Ordinances of Monroe
County, Florida, be amended so that such Section shall read as
follows:
"(b) Service panels, meters and equipment shall
not be located in closets, bathrooms, under stairs,
behind doors, or in any location which shall cause
it to be not readily accessible or create a hazzard
to life or property."
Section.7. That Subsection (c) of Section 6-151 of Chapter 6,
Buildings and Construction, of the Code of Ordinances of Monroe
County, Florida, be amended so that such Section shall read as
follows:
"(c) All buildings with more than six (6) meters,
and two (2) or more stories in height must have a
meter room, at least four (4) feet wide and seven
(7) feet high, the length determined by the length
of assembled equipment plus 30% for future use.
Meter room to be of CBS construction and concrete
roof, or to specifications of power company."
Section 8. That Section 6-154 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-154. Wiring methods.
(a) Approved rigid conduits, intermediate metal
conduit IMC, steel tube EMT, rigid non-metalic
conduit PVC, surface metal raceways, underfloor
raceways, cast -in -place raceways, wireways, and
busways shall be required for all wires used to
conduct current for light, heat or power, in
the wiring of all new buildings and additions
thereto WITHIN the limits of Monroe County.
(b) PVC Schedule 40 with bond wire may be used
in concrete slabs and underground in accordance
with Article 300-5-197, National Electric Code.
(c) A six (6) foot section of greenfield may
be used where necessary.
(d) Two (2) locknuts, one inside and one outside
of boxes and cabinets shall be required on all
conduit jobs. Approved bushings shall be used on
any conduits entering or leaving a panel or cabinet
if the conduits contain #8 wires or larger, where
concentric knockouts are used and do not utilize
the largest knockout, a grounding bushing bonded
to the box is required on metal conduit.
(e) Romex in single family or duplex residences
only. Romex #12 minimum with ground -copper may be
used in all wood frame construction only, including
the wood floor. Romex run in all wood frame
construction with concrete floor is to be minimum
twelve (12) inches above concrete. When runs are
parallel with joist they must be strapped along
side of joist. When crossing joist, the runs shall
be on a running board or bored holes, 1/3 the
distance from a bearing wall or may lay on top of
joist if less than one (1) foot between joist and
rafter. In stud walls, holes shall be bored in
center of studs, and must have at least thirty
(3) inches clearance from bottom of joist to
ground if run under wood floors on running boards.
There are not to be any junction boxes in attic
or any other location unless absolutely necessary.
If used, junction boxes are to be readily accessible.
Minimum size of metalic romex boxes: 3" X 2" X 22"
only allows 1-12-2 cable. Maximum size: 3" X 2"
X 32", maximum 6 wires in box (#12) over 6 wires
use 4" square box or with extension box. See
National Electric Code, Article 370-6. Leave
4 inch of the sheath on romex showing inside of
the box. Allow two (2) spare circuits in panel
for future use. All joints are to be made up
and plaster rings on before calling for inspection.
Romex sheath must be skinned about six (6) inches
before clamping in box, not after, and ground wires
made up and bolted to box."
Section 9. That Subsection (c) of Section 6-157 of Chapter 6,
Buildings and Construction, of the Code of Ordinances of Monroe
County, Florida, be amended so that such Section shall read as
follows:
"(c) The service grounding conductor shall be
run from the meter or main switch enclosure to
ground, an approved driven grounding copper rod
using an approved, exposed; accessible, ground
fitting making an electrical connection with the
grounding conductor. Also, from the same ground
rod a #6 must be bonded to copper water system in
the building. See Article 250-80 of latest edition
of National Electrical Code."
Section 10. That Subsection (d) of Section 6-157 of Chapter 6,
Buildings and Construction, of the Code of Ordinances of Monroe
County, Florida, be amended so that such Section shall read as
follows:
"(d) Service and grounding conduits shall be
securely fastened to the building using approved
straps. Wood plugs used in brick or concrete
will not be approved."
Section 11. That Chapter 6, Buildings and Construction, of
the Code of Ordinances of Monroe County, Florida, be amended by
adding a Section to be numbered Section 6-157(j), to read as
follows:
"(j) On buildings where a riser does not extend
three (3) feet above roof and eye bolt must be
installed within three (3) feet of service head
that will hold the strain of the power company's
drop from their pole to building and must be
approved by the Power Company."
Section 12.
That Chapter 6, Buildings and Construction, of
the Code of Ordinances of Monroe County, Florida, be amended by
adding a Section to be numbered Section 6-157(k), to read as
follows:
"(k) Services, disconnect, panel, metering
equipment, etc.... shall not be mounted on break-
away walls (branch circuit general purpose outlets
only) . "
Section 13.
That Subsection (c) of Section 6-159 of Chapter 6,
Buildings and Construction, of the Code of Ordinances of Monroe
County, Florida, be amended so that such Section shall read as
follows:
"(c) Permanently installed motors above i horse
power and up to and including five (5) horse power
will be connected to a 230 volt, single phase service
or three (3) phase service."
Section 14. That Section 6-160 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-160. Metal conduit and fittings. All metal
conduit and fittings, unless of corrosion resisting
metal, shall be galvanized, sheradized or shall
have an equivalent coating of corrosion resisting
metal. No aluminum conduit, Article 345 - National
Electric Code, intermediate metal conduit "IMC" NOT
to be used for service mast."
Section 15. That Section 6-161 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-161. Electric range and water heater wiring.
(a) All electrical water heaters or other
heating appliances up to and including 1,650 watts
may be connected 120 volts, over 1,650 watts to be
connected 230 volts.
(b) All electric ranges shall be connected 115-
230 volts, three (3) wire and grounded."
Section 16.
That Section 6-165 of Chapter 6, Buildings and
Construction, of the Code of Ordinances of Monroe County, Florida,
be amended so that such Section shall read as follows:
"Sec. 6-165. Miscellaneous specifications.
(a) In the case of individual oven and surface
units (built-in ranges) will be permissible to
install a minimum of three (3) #8 conductors to
each of the units, provided that each run is
separately circuited with proper overcurrent
protection for the size of conductors and
equipment used.
(b) All wiring in conduit shall be open for
roughing inspection before switches, panel fronts,
receptacles or covers are installed.
(c) All wiring in beauty parlors shall be
installed in rigid conduit or EMT, and all equipment
used therein shall be connected to the system with
three (3) wire cords, plugs and receptacles, grounding
the frames of all such equipment.
(d) A separate sign circuit shall be installed in
all store or public buildings (new or remodeled).
This sign circuit must be installed in a separate
conduit from panel.
(e) Sign transformers shall not be placed in
attic spaces. Drain holes shall be provided in metal
transformer boxes, and when exposed to the weather
the boxes shall be reamed or otherwise trimmed to
remove burrs or rims that would hold water in the
enclosure. If mounted on the roof, the transformer
enclosure shall be elevated at least two (2) inches
above the roof. Wood shall not be used to mount
or elevate the transformer enclosure. The transformer
shall be rigidly fastened to the metal enclosure.
(f) Maximum number of outlets per circuit on
commercial or residential buildings. Residences -
10 points to circuits, lights - 1 point, duplex
receptacles - 2 points, except kitchen and dining
room - only 2 receptacles to circuit. Commercial -
6 points to circuit, except special circuits.
(g) All kitchen receptacles for general use -
only 2 per circuit and 2 circuits are required.
Fixed appliances such as refrigerator, dishwasher,
disposal, trashmasher, freezer, etc .... shall be on
separate circuits.
(h) Light outlets in clothes closets must be
eighteen (18) inches from shelving or stored
combustible material. Receptacles no higher than
one (1) foot from the floor will be permitted in
clothes closets for the use of approved mildew lights
or heaters.
(i) Branch circuits in all installations feeding
all outlets and switches shall not be smaller than
#12 copper wires.
(j) For every eighty (80) feet of a continuous
run of wire, the conductor size must be increased
one size.
(k) Troughs or auxiliary gutters shall be so
installed that main service and branch circuit
wiring will not enter the same trough. Where branch
circuit wiring shall pass through the main service
trough, the branch circuit CONDUIT shall pass through
the trough preventing any contact between the branch
circuit and the main service conductors.
(1) Portable cords attached to music boxes, pinball
machines, soft drink dispensers and other similar
equipment, shall not exceed six (6) feet in length
when measured from the equipment to the outlet
supplying the current. Cords shall not be nailed
down, tacked, stapled or held with strings or other
supports but shall be left free and clear.
(m) Plaster rings shall be placed on all four
(4) inch or larger boxes in concealed installations.
(n) Requirements in multiple dwellings: On new
buildings AND REWIRED BUILDINGS, no branch circuits
shall be connected to serve more than one (1) apartment.
Distribution panels shall be located in the apartment
they serve or in a public space. IN RESIDENCES, PANELS
SHALL NOT BE LOCATED IN CLOTHES CLOSETS, BEDROOMS,
UNDER STAIRS, KITCHEN CABINETS, BEHIND DOORS or ANY
PLACE THAT IS NOT READILY ACCESSIBLE.
(o) Attic fans shall be on a separate circuit
run direct from panel to the fan switch.
(p) (Handy) 2 X 4 X 12" boxes only three (3)
conductors plus device will be allowed.
(q) Each window type air-conditioning unit shall
be connected to a separate circuit using wires not
smaller than # 12 copper wire and SHALL BE GROUNDED.
(r) Stairway lighting is required and shall be
controlled by three (3) or four (4) way switches
located at top and bottom of stairways; except in
multiple dwellings or apartments or other public
buildings where the stair lighting is controlled
on special hall, corridor or house circuits.
(s) In new construction or remodeling where
ceiling fans are to be installed, a 4" X 4" or equal
is to be installed to support the fan.
(t) In the wiring of new buildings, two (2)
spare circuits shall be provided.
(u) Circuit identification: The contractor shall
identify all branch circuits at the panel showing
the outlets so served BEFORE CALLING FOR FINAL INSPECTION.
(v) Every electrical contractor shall stencil or
provide a decal with the contractor's name and
address and phone number on the main switch or panel.
(w) Sub -feeder conductors to sub -panels shall
be protected at the original point of the sub -feed
for the maximum current carrying capacity of the
sub -feed conductors. The sub -feed conductors shall
be sized to meet the current consuming capacity of
the connected load.
(x) Design of customer owned vaults must be
approved by local power company prior to construction
and specification will be furnished by the power
company in advance.
(y) Separately metered conductors shall not be
installed in the same raceway except in gutters
in meter room. The line and load shall not be in
the same raceway.
(z) In multiple units the feeders shall be considered
the same as services.
(aa) A request for inspection of electrical work,
such as rough -in, equipment installation, final
inspection, etc...shall be made at the office of
the Electrical Inspector as soon as the job is ready.
(bb) The request for inspection must be made
by the person, firm or corporation installing the
wiring. Failure to request such inspections constitutes
a violation of this code, and could cause your license
to be suspended after a hearing of the CONTRACTOR'S
LICENSING BOARD.
(cc) PVC raceways shall not be used on services
extended up poles or side of buildings and all PVC
must have bond wires of proper size installed with
conductors. All PVC must be schedule 40 or better.
(dd) No PVC to be used exposed outdoors above
ground unless approved for the purpose, or encased
in minimum two (2) inches of concrete.
(ee) PVC may be used in wet locations indoors,
if not subject to physical damage.
(ff) All service grounds must be enclosed in
rigid metal conduit with thread hub type ground
fitting with minimum #6 copper wire.
(gg) NO WATER PIPE OR FITTING SHALL BE SUBSTITUTED
FOR ELECTRICAL CONDUIT AND FITTING.
(hh) Sub -feeds to mobile homes must be in conduit
with wire capacity of the main panel inside of trailer.
(ii) All backing boards for Electrical equipment
must be exterior plywood and painted on both sides.
Qj) No junction boxes in attic or concealed
places unless there is at least thirty (30) inches
of crawl space and not over twenty (20) feet from
access hnle_
(kk) No direct burial cable for any purpose!
Underground primaries over 250 volts across phases
in PVC Schedule 40 must be at least thirty (30)
inches deep with a minimum of six (6) inches concrete
on all sides or as National Electric Code requirements.
(11) All sub -feeds in apartments, stores, etc...
to be a minimum of 14 inches raceway from meter room
to panels.
(mm) All underground services 225 AMP or under,
from pole to building must have fuse or breaker
protection at the pole. All conduits must be offset
to hug poles or sides of surface they run on.
(nn) No romex in buildings with metal floors
or walls. See requirements on romex.
(oo) When using existing meter base for a new
sub -feed, a disconnect must be added along side
of proper size and service wire from meter to service
head increased if necessary.
(pp) All conductors must be copper (no copper
clad aluminum or aluminum). Minimum #12, no aluminum
conduit underground - slabs or eighteen (18) inches
of ground.
(qq) There must be a licensed Monroe County
Master Electrician in charge of and supervise any
job where any electrical work is being installed,
except a home owner doing his own work.
(rr) There must be a licensed Monroe County
Journeyman Electrician on the job at all times any
electrical work is being done. The journeyman must
be employed by a Master Electrician - Contractor.
An apprentice must have a Master or Journeyman present
at all times he is working.
(ss) Home owners cannot engage a journeyman or
apprentice without an electrical contractor.
(tt) All electrical conduits in poured concrete
must be PVC Schedule 40 and tied down to keep from
floating when poured.
(uu) Conduit, PVC or any raceway that runs on the
surface must hug the surface and be strapped per
latest edition of National Electric Code. Stand
offs may be used when needed. When leaving the
ground level up a pole or the side of a building,
there must be at least one strap no more than two
(2) feet from ground level.
(vv) Voltage to under -water pool lights shall
not be more than twenty-four (24) volts.
(ww) Lighting wires or rods with 6'-0" of
grounding rods are to be bonded to the grounding
rod per National Electrical Code. 250-46."
Section 17. That Chapter 6, Buildings and Construction, of
the Code of Ordinances of Monroe County, Florida, be amended by
adding a Section to be numbered Section 6-166, to read as follows:
"Sec. 6-166. Penalty for Violation.
Any person violating or permitting to be violated
any of the provisions of this regulation shall upon
conviction before the County Court, be punished by a
fine of not more than FIVE HUNDRED ($500.00) DOLLARS,
or by imprisonment in the County Jail not exceeding
SIXTY (60) DAYS, or both such fine and imprisonment."
Section 18. If any section, subsection, sentence, clause or
provision of this Ordinance is held invalid, the remainder of this
Ordinance shall not be affected by such invalidity.
Section 19. All ordinances or parts of ordinances in conflict
with this Ordinance are hereby repealed to the extent of said conflict.
Section 20.
The provisions of this Ordinance shall be included
and incorporated in the Code of Ordinances of the County of Monroe,
Florida, as an addition or amendment thereto, and shall be appro-
priately renumbered to conform to the uniform numbering system of
the Code.
Section 21. This Ordinance shall take effect immediately upon
receipt of official notice from the Office of the Secretary of State
of the State of Florida that this Ordinance has been filed with
said Office.
BOARD OF COUNTY COMMISSIONERS
OF MONROE COUNTY, FLORIDA
By
Ma:y'isr Chatrman T .....
(SEAL)
Attest:
_IHITr
RhUn L
Clerk
ADOPTED: SEPTEMBER 30, 1983
FILED WITH SECRETARY OF STATE: OCTOBER 13, 1983
EFFECTIVE DATE:
NOTICE OF INTENTION TO CONSIDER
ADOPTION OF COUNTY ORDINANCE
NOTICE IS HEREBY GIVEN TO WHOM IT MAY CONCERN that on
Friday, September 16, 1983, at 10:00 A.M. in Courtroom B, Monroe
County Courthouse Annex, 500 Whitehead Street, Key West, Monroe
County, Florida, the Board of County Commissioners of Monroe
County, Florida, intends to consider the adoption of the
following County Ordinance:
ORDINANCE NO. -1983
AN ORDINANCE OF THE COUNTY OF MONROE,
FLORIDA, PROVIDING THAT THE CODE OF
ORDINANCES OF MONROE COUNTY, FLORIDA, BE
AMENDED BY REVISING CHAPTER 6, BUILDINGS AND
CONSTRUCTION, OF SAID CODE; REFLECTING
CHANGES IN THE LATEST SUPPLEMENT TO THE
NATIONAL ELECTRICAL CODE; PROVIDING FOR THE
SEVERABILITY; PROVIDING FOR INCLUSION IN THE
CODE OF ORDINANCES OF MONROE COUNTY, FLORIDA,
AND PROVIDING FOR AN EFFECTIVE DATE.
DATED at Key West, Florida, this 12th day of August, A.D. 1983.
RALPH W. WHITE
Clerk of the Circuit Court
of Monroe County, Florida
and ex officio Clerk of the
Board of County Commissioners
of Monroe County, Florida
(SEAL)
PROOF OF PUBLI�
THE FLORIDA KEYS KEYNOTER
Published Weekly
MARATHON, MONROE COUNTY, FLORIDA
STATE OF FLORIDA )
COUNTY OF MONROE )
Before the undersigned authority personally appeared
Office Manager
Judith E. Proulx
, who on oath, says
that he is of The FLORIDA KEYS KEYNOTER, a weekly newspaper published at Marathon, in
Monroe County, Florida; that the attached copy of advertisement, being allotice Of Intention to Consider Adoption of
Ordinance
IN THE MATTER OF Revising Chapter 6, Buildings & Construction County in the
newspaper in the issues of
August 25, 1983
Court, was published in said
Affiant further says that the said FLORIDA KEYS KEYNOTER is a newspaper published at Mara-
thon, in said Monroe County, Florida, and that the said newspaper has heretofore been continuously
- - - - — - — — -- - - - — ---- — -- -- -- ----I
published in said Monroe County, Florida, each week (on Thursday) and has been entered as second
class mail matter at the post office in Marathon, in said Monroe County, Florida, for a period of one
year next preceding the first publication of the attached copy of advertisement; and affiant further
says that he has neither paid nor promised any person, firm, or corporation any discount, rebate, com-
mission -or refund -for the purpose of securing this advertisement for publication in the said newspaper.
(SEAL)
-SWORN TO AND SUBSCRIBED BEFORE ME THIS �=!L
` , o
DAY'OA.D. 19
NOTARY PLTVC S ,,!7 OF FLOR.tnS
h1Y Comm I SS I ON E?.P I GAS MAY -31 19.8�
bGNDED THRU GFNI2AI INKIiDAarc II, -SIN
of
ORDINANCE. NO. -1963'
An Ordinance -of the County
of Monroe, Florida,. rovid-
I ino that _ the Code of Ordi-
nances of Monroe County,
Florida be amended by re-
vising Chapter 6, Buildiny s
and Construction. of Bald
National Electrical - Co- —
Providing for the severabilr
ly; Providing for inclusion In
the Code of Ordinances of
Monroe County, Florida,
and Providing for an effec-
tive date.
This 12ED-day of Augus.oAD.
1983.
oheCcitCort -Clerk f Circuit Court
of Monroe County,. Flprida
and ex ofiicfo Clerk
of the Board of
County Commissioners of
Monroe County, Florida
Publish: August 25, 1983
Florida Keys Keynoter
PROOF OF PUBLICATION
oX
SERVING THE UPPER KEYS
BOX 1197, TAVERNIER, FL. 33070
STATE OF FLORIDA )
COUNTY OF MONROE )
Before the undersigned authority personally appeared W.B. WOLFF
, who on oath, says that he is EDITOR & PUBLISHER
of THE REPORTER, a weekly newspaper published at Tavernier, Monroe County, Florida;
that the attached copy of advertisement, being a LEGAL NOTICE
IN THE MATTER OF NOTICE OF INTENTION
in the Court, published in said
newspaper in the issues of //
5/83
Affiant further says that the said REPORTER is a
newspaper published at Tavernier, in said Monroe Count' NOTICE OF*�NT 10 TO CONSIDER
Florida, and that the said newspaper has heretofore bei ADOPTIONOFCOU TYORDINANCE
continuously published in the said Monroe County, Flor NOTICE IS HEREBY GIVEN TO WHOM IT MAY CONCERN that on
Friday, September 16, 1983, at 10:00 A.M. in Courtroom B, Monroe County
Courthouse Annex, 500 Whitehead Street; Key West, Monroe County, Florida, the
each week (on Thursday) , and has been entered as seconl Board of County Commissioners of Monroe County, Florida, intends to consider
class mail matter at the Post Office in Tavernier, in .,
the adoption of the following County Ordinance:
ORDINANCE NO. -1983
County of Monroe, Florida, for a period of one year nea
AN ORDINANCE OF THE COUNTY OF MONROE, FLORIDA, PROVIDING
preceding the first publication Of the attached Copy Of THAT THE CODE OF ORDINANCE OF MONROE COUNTY, FLORIDA, BE
AMENDED BY REVISING CHAPTER 6, BUILDINGS AND
advertisement; and affiant further says that he has nei CONSTRUCTION OF SAID CODE; REFLECTING CHANGES IN THE
LATEST SUPPLEMENT TO THE NATIONAL ELECTRICAL CODE;
paid nor promised any firm, person, or corporation any PROVIDING FOR THE SEVERABILITY; PROVIDING FOR INCLUSION IN
THE CODE OF ORDINANCES OF MONROE COUNTY, FLORIDA, AND
discount, rebate, commission Or refund for the purpose PROVIDING FOR AN EFFECTIVE DATE.
securing this said advertisement for publication in the DATED AT Key West,Florida, this 12thday ofAugust, A.D.1983.
RALPH W. WHITE
said newspaper. I Clerk of the Circuit Court
of Monroe County, Florida
and ex officlo Clerk of the
Board of County Commissioner:
UH of Monroe County, Florid.
SEAL Published: 8125/83
- _ The Reporter
;S.WORK TO AND SU SC I BED BEFORE ME THIS Tavernier, Fla.33070 - -
lsi DAY of SEPTEIVIBER A.D..19 83
NOTARY PUBLIC
~ Plptary Public, State of Florida at Lard
MY COMMISSION EXPIRES:_ Plly r- missien F;,,^fires Bee 26, 1986
hnnrlari by Firiality 2 f)anncit rn_ of Marvland
October 17, 1983
' I H E STAY
� EO
� n
W
u
4, .,, r'OD
FLORIDA DEPARTMENT OFSTATE
George Firestone
Secretary of State
Honorable Ralph W. White
Clerk of Circuit Court
S00 Whitehead Street
Key West, Florida 33040
Attention: Ms. Virginia M. Pinder
Dear Mr. White:
Pursuant to the provisions of Section 125.66, Florida Statutes,
this will acknowledge:
NK/
1. Receipt of your letter/s of
and certified copy/ies of
County Ordinance/s No./s
2.
Receipt of
relative to:
(a)
October 13
Monroe
83-20 and 83-21
County Ordinance/s
which we have numbered
(b)
which we have numbered
3. We have filed this/these Ordinance/s in this office
on October 17, _1983.
4. The original/duplicate copy/ies showing the filing date is/are
being returned for your records.
Cordially,
!-'
(N1rs . - Nancy Kavanaugh
Chief, Bureau of Laws
FUDRIDA-State of the Arts